TW-80 16 mm2

Description

Description

Standards

  • Product
    IEC 60227-1; IEC 60227-2; IEC 60227-3; IEC 60228; NTP 370.252; NTP-IEC 60228
  • Test
    IEC 60332-1-2; IEC 60811-401; IEC 60811-402; IEC 60811-501; IEC 60811-504; IEC 60811-505; IEC 60811-506; IEC 60811-508; IEC 60811-509; UL 2556

 

Application:

In fixed installations, in buildings, dry or wet indoor locations. Typically installed in pipe.

 

Construction:

1. Conductor: Compact soft copper, class 2.

2. Insulation: Compound polyvinyl chloride PVC.

 

Main characteristics:

Good dielectric strength, resistance to moisture, grease, oil and heat up to serving temperature. Flame retardant VW-1.

Cross section:

From 16 mm2 up to 185 mm2.

Marking:

INDECO S.A. TW-80 - 450/750 V - Section - OIL RESISTANCE II, DOES NOT PROPAGATE THE FLAME VW-1, MADE IN PERU - Year - Sequential length.

Packing:

Non returnable wooden reels.

Colour:

To costumer request.

 

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP 370.252: Thermoplastic and thermoset insulated cables of rated voltages up to and including 450/750 V.

 

International standards

IEC 60228: Conductors of insulated cables.

IEC 60227-1: Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V - General requirements.

IEC 60227-2: Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V - Test methods.

IEC 60227-3: Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V - Non-sheathed cables for fixed wiring.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.

UL 2556: Wire and Cable Test Methods. Section 9.4: VW1 (Vertical-Specimen) Flame Test.

IEC 60811-401: Thermal ageing methods. Ageing in an air oven.

IEC 60811-402: Water absorption test.

IEC 60811-501: Tests for determining the mechanical properties of insulating and sheating compounds.

IEC 60811-504: Bending test at low temperature for insulation and sheaths.

IEC 60811-505: Elongation at low temperature for insulations and sheaths.

IEC 60811-506: Impact test at low temperature for insulations and sheaths.

IEC 60811-508: Pressure test at high temperature for insulations and sheaths.

IEC 60811-509: Test for resistance of insulations and sheaths to cracking (heat shock test).

BENDING RADIUS WHEN INSTALLED IN L.V.

R=Dxf

R: Bending radius when installed (mm)

D: Diameter over sheath or over insulation (when it has not sheath) (mm)

f: Multiplicative factor; given the following table:

Bending radius factor LV

CALCULATION OF CURRENT CONDITION: BUILDING WIRE L.V.; 80°C

CURRENT CAPACITY VALUES AND CURRENT CALCULATION CONDITIONS BASED ON IEC 60364-5-52:2009 :

TABLE B.52.2 (METHOD A1: Two single-core cables in conduit in a thermally insulated wall).
TABLE B.52.10 (METHOD F: Two single-core cables in the air in flat formation and in contact).
Maximum conductor temperature : 80°C.
Ambient air temperature : 30°C.

The above values were corrected with a correction factor for the operating temperature of 80°C.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulating material
PVC
Lead free
Yes
Colour
Customer Request
Conductor flexibility
Class 2 IEC 60228
Conductor shape
Compact stranded

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
16 mm²
Total number of wires
7
Conductor diameter
4.6 mm
Minimum insulation thickness
1.0 mm
Nominal outer diameter
6.7 mm
Approximate weight
165 kg/km
Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Dielectric strength
2.5 kV
Time of application Dielectric strength core to screen DC
5 min.
Max. DC resistance of the conductor at 20°C
1.15 Ohm/km
Nominal capacitance
1182.0 pF/m
Perm current rating in air 30°C
109 A
Perm current rating in duct 30°C
67 A

Usage characteristics

Usage characteristics

U.V resistance
UL 1581 - Sunlight Resistance
Flame retardant
UL 1581 VW1
Oil resistance
Oil resistance II
Maximum operating temperature
80 °C
Overload maximum core temperature
100 °C
Short-circuit max. conductor temperature
160 °C

Resources

Resources

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close