NYY(80°) 0,6/1 kV 3-1x6 mm2

Description

Description

Application:

General use as power cable. In low voltage distribution networks, industrial installations, buildings and operating centers. For fixed installations, in indoor areas (trays, ducts), in underground ducts or buried direct in ground, in dry or wet locations.

Construction:

1. Conductor: Soft copper, class 1 or class 2.

2. Insulation: Compound polyvinyl chloride PVC.

3. Outer sheath: Compound polyvinyl chloride PVC.

4. Tape: Polyester tape.

Main characteristics:

Good electrical and mechanical properties. The PVC outer sheath provides an adequate resistance to grease, oils and abrasion. better dissipation of heat allowing a higher current capacity. Flame retardant.

Cross Section:

From 6 mm2 up to 500 mm2.

Marking:

INDECO S.A. NYY(80º) 0,6/1 kV (2 or 3)-1x Section - Year - Sequential length.

Packing:

Non returnable wooden reels.

Colour:

Insulation: White.

Outer sheath: Black and white or Black, red and white or Black, red, blue.

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP-IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.

International standards

IEC 60228: Conductors of insulated cables.

IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.

IEC 60811-401: Thermal ageing methods. Ageing in an air oven.

IEC 60811-402: Water absorption tests.

IEC 60811-501: Test for determining the mechanical properties.

IEC 60811-504: Bending test at low temperature for insulation and sheaths.

IEC 60811-505: Elongation at low temperature for insulations and sheaths.

IEC 60811-506: Impact test at low temperature for insulations and sheaths.

IEC 60811-508: Pressure test at high temperature for insulation and sheaths.

IEC 60811-509: Test for resistance of insulations and sheaths to cracking.

ICEA S-95-658: Power cables rated 2000 volts or less for the distribution of electrical energy. Section 6.4.2: Oil: Oil Immersion Test.

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.

Calculation of Current Condition: Copper Conductor Double or Triple L.V.; 80°C

CURRENT CAPACITY VALUES AND CURRENT CALCULATION CONDITIONS BASED ON IEC 60364-5-52:2009 :

TABLE B.52.4 (METHOD D1: Buried ducts in contact).
TABLE B.52.4 (METHOD D2: Buried in contact).
TABLE B.52.10 (METHOD F: Air in flat formation and in contact).
TABLE B.52.10 (METHOD F: Air in tringular formation).

The cited values ​​were corrected with a correction factor for the maximum conductor temperature at 80°C.
Maximum conductor temperature : 80°C.
Ambient air temperature : 30°C.
Ground temperature : 20°C.
Depth of laying up to: 0,7 m.
Thermal resistivity of soil : 2,5 K.m/W.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulating material
PVC
Individual sheath
PVC
Lead free
Yes
Conductor flexibility
Class 1 & Class 2 IEC 60228
Conductor shape
Compressed
Insulation
XLPE
Type of conductor
Class 1
With Green/Yellow core
No
Sheath colour
Individual sheath White-Black-Red

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
6 mm²
Total number of wires
1
Conductor diameter
2.7 mm
Minimum insulation thickness
1.0 mm
Minimum outer sheath thickness
0.9 mm
Height
6.9 mm
Width
20.3 mm
Approximate weight
280 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Dielectric strength
3.5 kV
Time of application Dielectric strength core to screen AC
5 min.
Max. DC resistance of the conductor at 20°C
3.08 Ohm/km
Nominal capacitance
772.0 pF/m
Perm current rating in air 30°C
50 A
Perm. Current in duct 20°C
41 A
Perm. current rating in air 30°C - flat formation
50 A
Perm. current rating in air 30°C - trefoil formation
47 A
Permissible current rating buried 20°C
44 A

Usage characteristics

Usage characteristics

Oil resistance
ICEA S-95-658
Flame retardant
IEC 60332-1-2; FT1
U.V resistance
UL 2556 - Sunlight Resistance
Maximum operating temperature
80 °C
Overload maximum core temperature
100 °C
Short-circuit max. conductor temperature
160 °C
Midspan
Yes

Resources

Resources

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close