CAAI 0,6/1 kV Single Core

Products

CAAI 0.6/1 kV 16 mm2

Nexans ref. P00015898-3 - Country ref. 10037240

  • Phase Conductor Cross Section: 16 mm²
  • Phase Conductor Diameter: 5 mm
  • Nominal outer diameter: 7.4 mm
  • Approximate weight: 67 kg/km

 

CAAI 0.6/1 kV 25 mm2

Nexans ref. P00015899-4 - Country ref. 10037241

  • Phase Conductor Cross Section: 25 mm²
  • Phase Conductor Diameter: 5.8 mm
  • Nominal outer diameter: 8.2 mm
  • Approximate weight: 93 kg/km

 

Description

Description

Application

For installations of urban and rural connections, with voltages up to 1000 V.

STANDARDS

PRODUCT

NTP-IEC 60228; NTP 370.254; IEC 60228

TEST

IEC 60811-201; IEC 60811-401; IEC 60811-402; IEC 60811-501; 
IEC 60811-502; IEC 60811-507; IEC 60811-511

CONSTRUCTION

1. Conductor: Aluminum 1350, class 2.

2. Insulation: Cross linked polyethylene XLPE.

MAIN CHARACTERISTICS

Decreases energy theft, cross-linked polyethylene allows more current capacity and high insulation resistance, lower inductive reactance than with bare conductors, used in overhead distribution lines. Increased safety due to its mechanical strength and toughness of the insulation. Insulators are not necessary for installation. Resistance to abrasion, weather and sunlight.

CROSS SECTION

16 mm2 and 25 mm2.

MARKING

INDECO BY NEXANS CAAI 0,6/1 kV - (Section) - Year - Sequential length.

PACKING

Non returnable wooden reels.

COLOUR

Black, see core identification.

PRODUCT STANDARDS

NTP-IEC 60228: Conductors of insulated cables.

NTP 370.254: Cables for overhead distribution networks self-supporting XLPE insulated of rated voltages up to and including 0.6/1 kV.

TESTING STANDARDS

IEC 60228: Conductors of insulated cables.

IEC 60811-201: Measurement of insulation thickness.

IEC 60811-401: Thermal ageing methods -Ageing in an air oven.

IEC 60811-402: Water absorption test.

IEC 60811-501: Test for determining the mechanical properties of insulating and sheating.

IEC 60811-502: Shrinkage test for isolations.

IEC 60811-507: Hot elongation test for crosslinked materials.

IEC 60811-511: Measurement of hot melt index of polyethylene compounds.

BENDING RADIUS WHEN INSTALLED

R = f x D
R: Bending radius when installed (mm).
f: Multiplicative factor.
D: Cable nominal outer diameter (mm).

Calculation of Current Condition overhead secondary distribution

CALCULATION OF CURRENT CONDITION

Maximum conductor temperature : 90°C.
Ambient air temperature : 30°C.
Speed of cross wind: 2 km/h.
Bundled conductors.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum Alloy 1350
Insulating material
XLPE
Core identification
Rib markings
Conductor flexibility
Class 2 IEC 60228
Conductor shape
Compact stranded

Dimensional characteristics

Dimensional characteristics

Minimum insulation thickness
1.14 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV
Dielectric strength
4.0 kV
Time of application Dielectric strength core to screen DC
5 min.

Usage characteristics

Usage characteristics

Bending factor when installed
4 (xD)
U.V resistance
Yes
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Find a Distributor

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close