N2XOH-PC 0,6/1 kV Single-core; UV Resist.; METRIUM

Products

N2XOH-PC 0,6/1 kV 120 mm2

Nexans ref. P00040305-3 - Country ref. 10055493

  • Packaging: Cut to length (m)
  • Conductor cross-section: 120 mm²
  • Conductor diameter: 12.8 mm
  • Minimum insulation thickness: 1.2 mm
  • Diameter over Sheath: 17.4 mm
  • Approximate weight: 1187 kg/km
  • Permissible current rating buried/duct 20°C: 223 A

 

N2XOH-PC 0,6/1 kV 150 mm2

Nexans ref. P00040306-2 - Country ref. 10055494

  • Packaging: Cut to length (m)
  • Conductor cross-section: 150 mm²
  • Conductor diameter: 14.2 mm
  • Minimum insulation thickness: 1.4 mm
  • Diameter over Sheath: 19.4 mm
  • Approximate weight: 1451 kg/km
  • Permissible current rating buried/duct 20°C: 251 A

 

N2XOH-PC 0,6/1 kV 185 mm2

Nexans ref. P00040308-2 - Country ref. 10055495

  • Packaging: Cut to length (m)
  • Conductor cross-section: 185 mm²
  • Conductor diameter: 18.0 mm
  • Minimum insulation thickness: 1.6 mm
  • Diameter over Sheath: 23.9 mm
  • Approximate weight: 1706 kg/km
  • Permissible current rating buried/duct 20°C: 281 A

 

N2XOH-PC 0,6/1 kV 240 mm2

Nexans ref. P00040310-2 - Country ref. 10055497

  • Packaging: Cut to length (m)
  • Conductor cross-section: 240 mm²
  • Conductor diameter: 20.7 mm
  • Minimum insulation thickness: 1.7 mm
  • Diameter over Sheath: 26.8 mm
  • Approximate weight: 2271 kg/km
  • Permissible current rating buried/duct 20°C: 324 A

 

N2XOH-PC 0,6/1 kV 300 mm2

Nexans ref. P00040521-1 - Country ref. 10055641

  • Packaging: Cut to length (m)
  • Conductor cross-section: 300 mm²
  • Conductor diameter: 23.2 mm
  • Minimum insulation thickness: 1.8 mm
  • Diameter over Sheath: 29.7 mm
  • Approximate weight: 2822 kg/km
  • Permissible current rating buried/duct 20°C: 365 A

 

Description

Description

Application

In low voltage power distribution networks. Special application in places with poor ventilation, direct application in places with public attendance high. It can be installed in ducts in dry and wet places.

STANDARDS

PRODUCT

NTP-IEC 60228; NTP-IEC 60502-1; IEC 60228; IEC 60502-1

TEST

IEC 60332-1-2; IEC 60332-3-24; IEC 60754-1; IEC 60754-2; IEC 61034-2; UL 2556

CONSTRUCTION

1. Conductor: Flexible soft copper.

2. Insulation: Cross linked polyethylene XLPE.

3. Outer sheath: HFFR- UV halogen free thermoplastic compound.

MAIN CHARACTERISTICS

The cable has excellent electric properties. The cross-linked polyethylene insulation allows a higher power capacity current under any operation conditions, lower dielectric losses, high insulation resistance.

The outer sheath have the following characteristics: Fire retardant, low emission dense smoke and halogen free. Adequate resistance to oils. Resistance to sunlight.

The new attributes of this product are:

Greater flexibility, helping in the installation and handling process, due to its new configuration of conductors and flexible raw materials for insulations and coating.

Greater protection to the external cover, against dragging during the process of installation on non-smooth surfaces, guaranteeing compliance with the thickness of the same.

CROSS SECTION

From 120 mm2 up to 300 mm2.

MARKING

INDECO BY NEXANS N2XOH-PC 0,6/1 kV - Section - Year (- sequential length m. || sequential length m. + ).

PACKING

Non returnable wooden reels.

COLOUR

Insulation: Natural.

Outer sheath: Black-UV.

PRODUCT STANDARDS

NTP-IEC 60228: Conductors of insulated cables.

NTP-IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.

IEC 60228: Conductors of insulated cables.

IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.

TESTING STANDARDS

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.

IEC 60332-3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C.

IEC 60754-1: Test on gases evolved during combustion of materials from cables. Part 1: Determination of the halogen acid gas content.

IEC 60754-2: Test on gases evolved during combustion of materials from cables. Part 2: Determination of acidity (by pH measurement) and conductivity.

IEC 61034-2: Measurement of smoke density of cables burning under defined conditions.

UL 2556: Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc Tests- Sunlight resistance.

Calculation of Current Condition: Copper Conductor Single-core L.V.; Halogen Free 90°C

CURRENT CAPACITY VALUES AND CURRENT CALCULATION CONDITIONS BASED ON IEC 60364-5-52:2009 :

TABLE B.52.5 (METHOD D1: Buried ducts in tringular formation).
TABLE B.52.12 (METHOD F6: Air in flat formation and in contact).
TABLE B.52.12 (METHOD F5: Air in tringular formation).

Maximum conductor temperature : 90°C.
Ambient air temperature : 30°C.
Ground temperature : 20°C.
Depth of laying up to: 0,7 m.
Thermal resistivity of soil : 2,5 K.m/W.

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulating material
XLPE
Outer sheath
Halogen free thermoplastic compound - UV Resist.
Halogen free
Low content Halogen IEC 60754-1
Sheath colour
Black - UV

Electrical characteristics

Electrical characteristics

Dielectric strength
3.5 kV
Time of application Dielectric strength core to screen AC
5 min.

Usage characteristics

Usage characteristics

Gases corrosivity
Low Corrosivity IEC 60754-2
Smoke density
Low Smoke Emission IEC 61034-2
Flame retardant
IEC 60332-1-2; FT1
Fire retardant
EN IEC 60332-3-24 (cat C)
U.V resistance
UL 2556 - Sunlight Resistance
Metric marking
Double marking of sequential footage METRIUM
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close