PC NH-90 450/750 V 4 mm2 RJ

Description

Description

Application:

Special application in places with poor ventilation, where, in case of fire, the emission of corrosive, toxic gases and smoke threatens life and destroys electrical and electronic equipment. In case of fire, possible victims have higher chances of surviving because they don't breath in toxic gases and have good visibility to escape the area. They are usually installed in conduits and in indoor areas in tray. Not recommended for outdoor installations

Construction:

1. Conductor: Soft copper, class 2.

2. Insulation: Halogen free thermoplastic sliding material HFFR.

Main characteristics:

  • Fire retardant, zero dense smoke emission and halogen free.
  • Easy and fast opening due to its innovative OPEN FAST die-cut packaging.
  • Easy installation due to its sliding insulation, it does not need any type of lubricant for installation in pipes.
  • Easy to measure due to its double sequential marking called METRIUM which allows to quickly read the installed lengths.
  • Use of VIGICHECK technology product originality identification hologram.

Cross section:

From 1,5 mm2 up to 6 mm2.

Marking:

INDECO S.A. PC NH-90 450/750 V - Section - H07Z1-R TYPE 2 - Year - MADE IN PERU (- sequential length m. || sequential length m. + ).

Packing:

From 1,5 mm2 to 6 mm2 in standard 100 meter rolls with VIGICHECK hologram.

Colour:

Black, red, blue and white.

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP 370.252: Thermoplastic and thermoset insulated cables of rated voltages up to and including 450/750 V.

NTP 370.266-3-31: Low voltage electrical cables. Cable with nominal voltage less than or equal to 450/750 V - Part 3-31: Cables with special properties before the fire. Single core cables without cover with halogen-free thermoplastic insulation and low smoke emission.

NTP 370.264-7: Insulation, covering and coating materials for low voltage electrical power cables - Part 7: Halogen-free thermoplastic compounds for insulation.

International standards

IEC 60228: Conductors of insulated cables.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3:FT1 (Vertical-Specimen) Flame Test.

IEC 60332-3-24: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category C.

IEC 60684-2: Flexible insulating sleeving - Part 2: Methods of test.

IEC 60754-1: Test on gases evolved during combustion of materials from cables - Part 1: Determination of the halogen acid gas content.

IEC 60754-2: Test on gases evolved during combustion of materials from cables - Part 2: Determination of acidity (by pH measurement) and conductivity.

IEC 61034-2: Measurement of smoke density of cables burning under defined conditions.

Calculation of Current Condition L.V.; NH-90

CALCULATION OF CURRENT CONDITION

Calculation of current capacity based on NEC (National Electrical Code NFPA 70) table 310.16 and table 310.17.

Maximum conductor temperature : 90°C.
Ambient air temperature : 30°C.
 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulation
Halogen free thermoplastic material sliding
Colour
Red
Halogen free
Low content Halogen IEC 60754-1
Lead free
Yes
Conductor flexibility
Class 2 IEC 60228
Conductor shape
Insulating material
Halogen free thermoplastic material sliding
With Green/Yellow core
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
4 mm²
Total number of wires
7
Conductor diameter
2.4 mm
Minimum insulation thickness
0.8 mm
Nominal outer diameter
4.1 mm
Approximate weight
48 kg/km
Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Dielectric strength
2.5 kV
Time of application Dielectric strength core to screen AC
5 min.
Max. DC resistance of the conductor at 20°C
4.61 Ohm/km
Nominal capacitance
830.0 pF/m
Perm current rating in air 30°C
43 A
Perm current rating in duct 30°C
33 A

Usage characteristics

Usage characteristics

Gases toxicity
Zero toxicity to IEC 60684-2
Gases corrosivity
Low Corrosivity IEC 60754-2
Smoke density
Low Smoke Emission IEC 61034-2
Flame retardant
IEC 60332-1-2; FT1
Fire retardant
EN IEC 60332-3-24 (cat C)
Bending factor when installed
4 (xD)
Installation type
Indoor
Packaging
OPEN FAST - N’Roll 100 m
Metric marking
Double marking of sequential footage METRIUM
Minimum operating temperature
-40 °C
Maximum operating temperature
90 °C
Midspan
No
Overload maximum core temperature
100 °C
Short-circuit max. conductor temperature
160 °C

Resources

Resources

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close