THW-90 +PLUS 450/750 V 14 AWG AZ, R100

Description

Description

Copper cable with Low Smoke PVC insulation and ribbed surface, whose operating temperature is 90°C. General application in fixed installations, resistant to humidity and heat. The ribbed surface offers better cable sliding during installation.

Application:

Special application in those poorly ventilated residential environments in which a fire increases the possibility of survival of possible victims by having a good visibility for rescue and escape from the place due to: low emission of dense smoke, low emission of harmful gases and does not spread the fire. They are generally installed in pipes for fixed installations, in buildings, inside places with dry or humid environment and in general in all installations that require higher current capacity than the TW-80 +PLUS cable. Not recommended for outdoor installations.

Construction:

1. Conductor: Soft copper, class B.

2. Insulation: Compound polyvinyl chloride PVC Low Smoke.

From 14 AWG up to 10 AWG in double-layer insulation.

Main characteristics:

Good dielectric strength, resistance to moisture, grease and heat up to serving temperature. The insulation has the following characteristics when the cable is exposed to fire:

Low dense emission smoke: Delayed dense smoke emission.

Fire retardant according IEC 60332-3-25 CAT. D.

Gauge:

From 14 AWG up to 10 AWG.

Marking:

INDECO S.A. THW-90 +PLUS - Gauge(AWG) - Section(mm2) - 450/750 V - LOW SMOKE - DOES NOT PROPAGATE THE FIRE CAT. D - MADE IN PERU.

Packing:

Rolls of 100 meters or on non-returnable wooden reels.

Colour:

Black, white, red, blue.

National standards

NTP 370.250: Conductors of insulated cables.

NTP 370.252: Thermoplastic and thermoset insulated cables of rated voltages up to and including 450/750 V.

International standards

UL 83: Thermoplastic-Insulated Wires and Cables

IEC 61034-2: Measurement of smoke density of cables burning under defined conditions.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame Test.

UL 2556: Wire and Cable Test Methods. Section 9.4: VW1 (Vertical-Specimen) Flame Test.

IEC 60332-3-25: Test for vertical flame spread of vertically-mounted bunched wires or cables - Category D.

Calculation of Current Condition L.V.; 90°C

CALCULATION OF CURRENT CONDITION

Maximum conductor temperature : 90°C.
Ambient air temperature : 30°C.
 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Soft copper
Insulating material
PVC Low Smoke
Colour
Blue
Conductor flexibility
Class B
Insulation
PVC
With Green/Yellow core
No

Dimensional characteristics

Dimensional characteristics

Conductor cross-section (AWG/KCMIL)
14 AWG
Total number of wires
7
Conductor diameter
1.7 mm
Minimum insulation thickness
0.76 mm
Nominal outer diameter
3.4 mm
Approximate weight
27 kg/km
Conductor cross-section
2.08 mm²
Number of cores
1

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Dielectric strength
2.0 kV
Time of application Dielectric strength core to screen AC
1 min.
Max. DC resistance of the conductor at 20°C
8.97 Ohm/km
Nominal capacitance
641.0 pF/m
Perm current rating in air 30°C
35 A
Perm current rating in duct 30°C
25 A

Usage characteristics

Usage characteristics

Slightly halogenous
IEC 60754-1
Smoke density
Low IEC 61034-2
Flame retardant
UL 2556 VW1
Oil resistance
Oil resistance II
Fire retardant
EN IEC 60332-3-25 (cat D)
Maximum operating temperature
90 °C
Overload maximum core temperature
130 °C
Short-circuit max. conductor temperature
250 °C
Midspan
No
Reference
01

Resources

Resources

Documentation

PEP Ecopassport pdf — 4.6 MB

Dealer locator

Waiting…

No items found

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close